B&B Product Compatibility with Industrial Buss
[ back to compatibility chart ]

Reference:

B&B part number 485OP

Subject:

Modbus Compatibility

 

 

The model 485OP is compatible with Modbus, with the following restrictions:

  1. The 485OP must be connected to the Modbus port 2
  2. Modbus port 2 must be configured as an RS-485 port.
    (the default protocol for Modbus port 2 is RS-232)

The model 485OP will work with 2 and 4 wire systems.

modbusph1.GIF (9896 bytes)

modbusph2.GIF (7352 bytes)

Pin Function
1 RXD-
2 RXD+
3 TXD+
4  
5 Signal common
6 TXD-
7  
8 Shield
Pin Function
1 TXD+
2 RXD+
3 Signal common
4  
5  
6 TXD-
7 RXD-

Master Communication Cable

Interconnect Cables

mastercomm.gif (1915 bytes) interconnect.gif (1744 bytes)

 

International Headquarters
B&B Electronics
707 Dayton Road • PO Box 1040 • Ottawa, IL 61350
T 815-433-5100 F 815-433-5109
Europe, Middle East, Africa
B&B Electronics Ltd
10 Westlink Commercial Park, Oranmore, Co. Galway, Ireland
T 353.91.792444 F 353.91.792445
U.K. T 01926 851500

 

[Home] [Products] [Partners] [Support] [Tech Notes] [News] [About] [Contact] [Site Map]
Questions or Comments? Copyright © 2011 B&B Electronics